55 HVAC Visual Cards · 2026 A2L Edition

HVAC Field Cards

All 55 cards · Diagnose · Startup checklist · PT Chart · SH / SC · Formulas · Notes. Add the app to your Home Screen (PDF guide) · Download the 68-page PDF

The 55 cards

Every card from the 55 HVAC Visual Cards, exactly as it appears in the PDF. Tap a card to open it.

Open full size, or pinch to zoom.

Diagnose with 4 readings

Based on Card 34, The Diagnostic Matrix (Rheem cooling troubleshooting table). Tap High or Low for each reading.

The full matrix

Source: Rheem R-454B variable-speed unit (EXV). Other sources differ on some rows — signatures depend on the metering device and unit design. Always verify airflow and coil cleanliness before adjusting charge.
Common mistake: adding refrigerant because suction pressure is low — low airflow also lowers suction pressure.

Startup & Commissioning Checklist

Residential AC, heat pump & gas furnace. Your checks are saved in this browser, on this device, until you clear them.

Card numbers point to the matching card in the 55 HVAC Visual Cards. This checklist does not replace the manufacturer's installation instructions, the rating plate or local codes — where they differ, they win.

Wiring & Schematics

The electrical side, in the same format as the 55 cards.

🔒 Wiring & Schematics
Add the electrical side

30 visual cards: read unit wiring diagrams, wire thermostats for AC, heat pumps, two-stage and dual fuel, add a C wire, trace the safety chain, wire PSC and ECM motors, and troubleshoot no-cooling calls.

Get Wiring Cards · $17

One-time payment. Delivered to your inbox right away. 30‑day money-back guarantee.

PT Chart

Saturation pressure (psig) ↔ saturation temperature (°F). Linear interpolation between chart rows, 30 to 125°F only.

Chart (psig)

Use one chart consistently. Different published charts can differ by 1–4 psi for R-454B. When the equipment manufacturer specifies a chart, use theirs.

Superheat & Subcooling

Enter the gauge pressure and the line temperature. Saturation comes from the PT chart in this app.

Superheat (suction side)

Subcooling (liquid side)

Piston → superheat · TXV / EXV → subcooling (Carrier/Bryant rule). Check airflow first; charge with the system running at least 15 minutes and within the manufacturer's charging conditions.

Quick Formulas & Targets

From the cards in 55 HVAC Visual Cards.

Superheat
Suction line temp − evaporator saturation temp

Measured at the suction line. For R-454B, read saturation from the DEW column. Near-zero superheat means liquid may be reaching the compressor.

Subcooling
Condenser saturation temp − liquid line temp

Measured at the liquid line near the service valve. For R-454B, read saturation from the BUBBLE column. Target is on the rating plate.

Which method
Piston → superheat · TXV / EXV → subcooling

Carrier/Bryant rule. Check airflow first; charge with the system running at least 15 minutes and within the manufacturer's charging conditions.

Deep vacuum
500 microns

Carrier, Rheem and Lennox all call for 500 microns. Read the micron gauge far from the pump and run the decay test in the unit's manual.

Airflow
≈ 400 CFM per ton

Rheem guideline. Lennox: target temperature drop is based on return-air dry bulb and wet bulb (±3°F).

Run capacitor (under load)
µF = (start-winding amps × 2,652) ÷ volts across cap

Goodman method, 60 Hz. Compare with the tolerance printed on the capacitor. Live test: CAT III meter and PPE.

Job Notes

Simple notes saved on this device only (not online). Clearing the browser data deletes them.

Field reference. Always confirm with the manufacturer's data and the unit's rating plate.